Tilted Forum Project Discussion Community  

Go Back   Tilted Forum Project Discussion Community > The Academy > Tilted Knowledge and How-To


 
 
LinkBack Thread Tools
Old 03-04-2005, 12:28 PM   #1 (permalink)
Upright
 
Location: NEW JERSEY
Run electricity outside (to a shed)

Can anyone please help?

I have two sheds in my backyard, one old and one new, I would like to install electricity to both. I have only one electrical outlet on the exterior of my house, and it is located in the front of the house. I would like to do as much of this project myself as possible, without hiring a professional. I am not sure how to start, besides turning off all power to the house first. I do not know how to get the electricity from the main breaker in my basement, outside to the sheds or anywhere else I might want to install an outlet. My house is a split level model with a finished lower level. The sheds are approximately 30 feet from the breaker. I would like to install 1 or 2 light fixtures in each shed and 1 or 2 recepticals in each shed and on the exterior of the house. If I don't have to install the electricity directly to the breaker I would prefer that. I have a set of flood lights installed on the back exterior of the house, if I could somehow tie into this power line that would probably be ideal.

If any additional info is needed please let me know.

Thank you in advance for any and all advice.
__________________
Remember, where ever you go, there you are.
FEIGN is offline  
Old 03-04-2005, 01:02 PM   #2 (permalink)
Junkie
 
If you do this work yourself and something happens to your house or sheds your insurance will not cover it and they may cancel your coverage on the rest of your house.

I'm not saying that anything *WILL* happen, but you know ...

Anyway.

You'll probably want to dig a trench and run the circuits in conduit. It's not a difficult job ... but it IS hard work.

You'll want a 40-or 60-amp subpanel in at least the first shed that feeds from a 40-or 60-amp breaker in the main (house) panel. Even if I did it myself I would NOT use an existing circuit in the main house. I would definetly have a dedicated circuit with a sub-panel. It's just not safe to do it any other way. You may need to cut the power to the entire shed at some point.

I'd at least go to the bookstore and get a How-To book that is dedicated to wiring. The all-in-one how-to books won't go into enough detail. I have a book by Black and Decker that explains EXACTLY what you want to do.

http://www.amazon.com/exec/obidos/AS...005697-7615113

I'm not sure if the book in the link above is still the same as the one I've got ... but it's the same title and press.

Good luck.

BTW - I hired a licensed electrician to run the conduit and put in a 40-amp subpanel in my shed. It was about $500. After the inspection I installed the receptacles and lights myself.

Last edited by vanblah; 03-04-2005 at 01:04 PM..
vanblah is offline  
Old 03-04-2005, 08:51 PM   #3 (permalink)
Banned
 
You do not need a sub panel. If all you plan are a few lights and receptacles all you need is one 15 amp circuit. I don't know the US electrical code but in Canada you would need 2 conductor #14AWG cable (a cable is a group of wires (conductors) in a common casing) with sheathing rated for direct burial. We call it NMWU (the WU is for Wet Underground) It is like loomex (can't remember what you's call it in the US) but it has a thicker plastic coating and thicker insulation on the wires. If you suspect you may want to run lights and a saw or something run 2 circuits (3 conductor cable) to a regular octagonal junction box with a blank coverplate, split the circuits out of the box to your lights and receptacles.

I would hesitate to connect to an existing light circuit because it may already be loaded to the nuts. If you overload it you may repeatedly trip your breaker. Installing breakers in a panel is easy if you take one circuit all you need is a 15 amp single pole breaker. Connect the ground (bare copper) wire to the ground bus in the panel, connect the white wire to the neutral bus, connect the black wire to the breaker then push the breaker into place. Typically the wire end of the breaker clips onto a plastic (or painted metal) bar that is not energized then you push the other side onto the hot bus. Work on a hot panel is ot hard or dangerous if you pear rubber soled shoes and only have one hand in the panel and the other in your pocket you will not get zapped dead even if you try to.

Your trench should be minimum 24 inches deep in areas where there is no vehicular traffic, if you are crossing a driveway you have to go deeper (36") by code. Where you pop up out of the ground it is a good idea to put the cable in a conduit of some sort to keep the mice from eating the insulation and keep the weedeater from wailing the hell out of it. Those may not apply but if there is any doubt slide a short peice of black water line over it.

In Canada we have a book called "The elecrical code simpified" that runs about $11 that covers everything you need to kow to build a house and then some. Go down to home depot or a building supply store and ask if they have a simplified code book for residential instalations. Have a read and if you feel comfortable fly at it.

A 40 or 60 amp feed and panel is serious overkill. Not many years ago entire houses had 60 amp services for the entire house. To give you some idea, until recently my 1500 sq ft house only had 100amps, I could run all the lights, 2 ranges, 3 freezers, 2 electric water tanks, stereo, computer.....at the same time.

If you run 3 conductor #14AWG cable you can have 2 15 amp circuits. The Canadian Electrical code allows max. 80% loading on a circuit wich would allow 14 100watt ligh bulbs and one 40 watt bulb on each circuit. That's probably enough lights for your sheds with an entire circuit left over for the electric bong, stereo and chop saw.
Powderedmaggot is offline  
Old 03-04-2005, 09:08 PM   #4 (permalink)
Psycho
 
Location: Where the night things are
If the use is only for a few convenience outlets, the need for a sub-panel is questionable. Based on the 30 foot run, you can install a 20 amp branch circuit breaker in your existing main panel and run the branch feeder in #12 wire several ways, referring to table 300.5 Minimum Cover Requirements. A 12" burial depth is acceptable for type UF, with GFCI protection. If you'd like to use NM conduit, the burial depth is 18". With RM or IM conduit, the depth is 6". All of these depths are based upon no vehicular traffic over the burial run.

If you want to do more with this circuit than run a weedwhacker or power a bugzapper, then a sub-panel is in order, along with associated requirements. Note that any receptacles installed on the referenced branch feeder, if installed outside of the shed where defined as a wet location must have a protective cover as defined by 406.8(B)(1).
__________________
There ain't nothin' more powerful than the odor of mendacity -Big Daddy
kazoo is offline  
Old 03-04-2005, 09:17 PM   #5 (permalink)
Insane
 
nofnway's Avatar
 
Location: under the freeway bridge
I mostly agree with Powderedmaggot,.....if you just want lights 15 amp circuits would be fine..if you want to appliances or power tools...especially at the same time I would reccomend #12 circuits rather than 14. In my area they are requiring #12 in kitchens now and I can't tell you how many service calls I've gone on for people overloading 15 amp circuits with things like those little heaters or vacuum cleaners both of which draw close to the max amps for the circuit.

A 60 amp sub panel would definitely be overkill unless you planned on using heavy shop tools like welders etc...even then you would have more than you need.
__________________
"Iron rusts with disuse, stagnant water loses its purity and in cold water freezes. Even so does inaction sap the vigor of the mind"
Leonardo Da Vinci
nofnway is offline  
Old 03-04-2005, 09:18 PM   #6 (permalink)
Psycho
 
Location: Where the night things are
Powderedmaggot, would you care to back up your citations with NEC references as I have done? I'm intrigued to hear your explanation of two 15 amp convenience circuits using a common #14 AWG neutral.
__________________
There ain't nothin' more powerful than the odor of mendacity -Big Daddy
kazoo is offline  
Old 03-05-2005, 02:43 AM   #7 (permalink)
Psycho
 
Lots of good yet pretty damn confusing information in this thread. Poor fella if he wasn't scratching his head before I bet he is for sure by now ..... HAHA. Simplified here goes ....

Set down and think for a bit about what you are gonna be using outside. Think about the most you will ever be using outside at any given time. Will you need 220v or will 110v be sufficient? This will determine how big the circuit should be. Go to Lowes or Menards etc., and buy about 40-45' of the grey wire that can be burried underground[better to have a little more than you need}. What size you buy will be determined by the amout of power you feel you need outside. If your only gonna run a few power tools or a few lights then I would probably buy 10/2 with ground. Next you will want to dig the trench between the house and the first shed. If you never plan on digging in that area then 12"-24" should suffice. Next you will want to make your penetrations in the house and into the first shed and run the wire. If you bring the wire out of the ground where it will be exposed at anytime after you place the dirt back then you will want to place plastic conduit over the wire as most underground wire is not UV rated. Plastic conduit is cheap and easy to work with. You will not need to place conduit over the wire in your basement. Just be sure to seal the small hole you make to get the wire into the basement. You can make this hole into the block with a hammer or drill through the band board. Next go outside and hook everything up out there. You can either run the wire into a sub-panel as suggested in a earlier post or run it straight into the first outlet box. You will need the branch circuit to be GFCI protected {for safety} and this can be accomplished several ways. You can either buy a GFCI rated breaker {expensive} and install that in the main power box or you can simply buy a GFCI outlet {not so expensive} and install it in the first box if you aren't setting a small sub-panel and wire everything out of there. Problem with using one GFCI outlet is anytime you exceed the limit of that one GFCI outlet you will need to push the reset button. Personally, I think I would buy a 30 amp two pole breaker and place that in the house and a sub-panel for the shed then run the wire between the main panel and the sub panel. This will allow you to have 220v outside in the sheds in case you ever need it for whatever reason, to run a small welder or 220v appliance for instance. Next I would purchase two single pole 15 or 20 amp GFCI breakers for the subpanel {one for each shed} and install them. Now you have power outside. Next I would run all my wires in the sheds using 12/2 with ground using conduit to get the wire between the sheds via conduit or buying wire that was uv rated or burying it using the underground wire. Next step is hooking everything up.
Setting a sub panel gives you a couple advantages, one being everything is protected back to the house with the 30 amp breaker. Everything in the sheds is covered by the single pole breakers installed in the sub panel. This will lesson the walks back to the house to reset the breaker. If you do happen to accidently overload the circuit chances are the 20 amp single pole will trip before the 30 back in the main will. Sure cuts down on a lot of walking .... Hope that cleared a little of the confusion up. Good Luck.
scout is offline  
Old 03-05-2005, 07:27 AM   #8 (permalink)
Tilted
 
Location: You'd never guess..
You should defintely check with your local building department regarding this. Here, any electrical work (aside from putting in a new outlet or something relatively simple) must have a permit pulled and/or receive inspection, and all work must be done by a licensed electrician. If you have a buddy that's licensed, I'd go that route, otherwise you are looking at a myriad of possible complications if something goes wrong.
IowaEric is offline  
Old 03-05-2005, 05:57 PM   #9 (permalink)
Banned
 
Quote:
Originally Posted by kazoo
Powderedmaggot, would you care to back up your citations with NEC references as I have done? I'm intrigued to hear your explanation of two 15 amp convenience circuits using a common #14 AWG neutral.
My CEC book is at work but it is common practice to use 3 conductor cable to run 2 circuits. A kitchen spit receptacle is an example. You don't run 4#14 to them you only run 3#14 (2 hots and a neutral) if your loads are perfectly ballanced (very uncommon) there will be no current flowint in the neautral. if they are unballanced the only unballanced amount of current flows in the neutral.
Powderedmaggot is offline  
Old 03-05-2005, 08:19 PM   #10 (permalink)
Psycho
 
Location: Where the night things are
Quote:
Originally Posted by scout
Problem with using one GFCI outlet is anytime you exceed the limit of that one GFCI outlet you will need to push the reset button.
GFCI receptacles are NOT, repeat NOT overcurrent protective devices. They never were. I know you folks mean well, but I'm upset with some of the bad advice posted in this thread. The code is updated every three years, and if you don't attend training sessions to stay on top of these changes, I don't think you should be advising people. My cites are based on the 2005 NEC, and my work as a contractor, inspector, NFPA and IAEI member.
__________________
There ain't nothin' more powerful than the odor of mendacity -Big Daddy
kazoo is offline  
Old 03-06-2005, 01:17 PM   #11 (permalink)
Junkie
 
james t kirk's Avatar
 
Location: Toronto
Powdered is right on track.

The only thing I might add is a GFI breaker in the main panel.

You can run a piece of 14-3 NMWU which will provide for 2 circuits, the only thing is that you need the proper double breaker that ensures that you take one hot lead off of one phase, and the other hot lead off of the other phase. In that case you can use one neutral.

If you take both hot phases off of the same phase with one neutral, you will have a "neutral overload" situation. This is impossible to do if you use the double 15 amp breaker however because the hot terminals in the breaker panel are staggered so that no two adjacent terminals are from the same phase.

The only thing I might add is that if if the run is over so many feet, you will experience a voltage drop due to the length of the conductors and you should switch from a 14-3 to a 12-3 NMWU.

Last edited by james t kirk; 03-06-2005 at 01:22 PM..
james t kirk is offline  
Old 03-06-2005, 08:21 PM   #12 (permalink)
Banned
 
Quote:
Originally Posted by kazoo
and my work as a contractor, inspector, NFPA and IAEI member.
And you don't know that you can run 2 circuits with 3 conductor cable????!!!!
Powderedmaggot is offline  
Old 03-07-2005, 10:15 AM   #13 (permalink)
Upright
 
Location: NEW JERSEY
Thank you all so much for the tips and advice. I greatly appreciate it. I think my best course of action will be to hire an electrician I can trust and have him let me do whatever work I can by myself (i.e. drilling, trenches, running wire etc...) to keep the cost down, and leave the technical stuff to a licensed, and insured, professional. Thank you all again for helping me realize that this is a job I definitely don't want to tackle by myself.

Thank you all again very much.
You have been very helpful.
__________________
Remember, where ever you go, there you are.
FEIGN is offline  
Old 03-07-2005, 09:17 PM   #14 (permalink)
Insane
 
LewisCouch's Avatar
 
Location: Pacific NW
Quote:
Originally Posted by Powderedmaggot
And you don't know that you can run 2 circuits with 3 conductor cable????!!!!
Logically this is sound, however, only if you use breakers which are on opposite phases. If you are unlucky enough to choose the same phase when wiring two different breakers, you're risking a fire if you overload the neutral. If you must do this (it would never pass inspection in my state), definitely use a double pole breaker.

The original poster has made a wise decision.
__________________
"The gift of liberty is like that of a horse, handsome, strong, and high-spirited. In some it arouses a wish to ride; in many others, on the contrary, it increases the desire to walk."

-- Massimo d'Azeglio
LewisCouch is offline  
Old 03-10-2005, 10:26 PM   #15 (permalink)
Psycho
 
Location: Where the night things are
Quote:
Originally Posted by Powderedmaggot
And you don't know that you can run 2 circuits with 3 conductor cable????!!!!
Yes, I'm aware that it can be done, however I prefer to err on the side of caution. As LewisCouch mentioned, a double breaker must be used, and care should be taken to prevent the OP or similar individual from confusing that with a "double skinny".

Discussing the question of the OP with other members, it was stressed that a separate disconnecting means for all ungrounded conductors (a two-pole switch) be provided within the outdoor shed, located higher than normal placement but not over the 6'7" rule such that power could be disconnected within the shed without travel to the main panelboard.

Beyond that, the only other concern expressed was that equipment or service with ground potential not be within the same shed(s), e.g. telco, without proper bonding requirements being observed under article 250.
__________________
There ain't nothin' more powerful than the odor of mendacity -Big Daddy
kazoo is offline  
 

Tags
electricity, run, shed

Thread Tools

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On



All times are GMT -8. The time now is 05:03 AM.

Tilted Forum Project

Powered by vBulletin® Version 3.8.7
Copyright ©2000 - 2024, vBulletin Solutions, Inc.
Search Engine Optimization by vBSEO 3.6.0 PL2
© 2002-2012 Tilted Forum Project

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255 256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 289 290 291 292 293 294 295 296 297 298 299 300 301 302 303 304 305 306 307 308 309 310 311 312 313 314 315 316 317 318 319 320 321 322 323 324 325 326 327 328 329 330 331 332 333 334 335 336 337 338 339 340 341 342 343 344 345 346 347 348 349 350 351 352 353 354 355 356 357 358 359 360